FIRE RESISTANT HALOGEN FREE CABLES Technical Data sheet
 

 

 acrobat reader_50x50  

APPLICATIONS

HTKSH FE180 PH90/E30-E90 and HTKSHekw FE180 PH90/E30-E90 fire resistant and halogen free cables intended for interconnections between switching and transmission equipment, for analogue or digital data transmission in industrial electronics and control applications all in objects of sharp fire protection requirements, particularly in fire alarm and fire automatic control systems.

The cables are certified by Scientific and Research Centre for Fire Protection - National Research Institute (Centrum Naukowo-Badawcze Ochrony Przeciwpożarowej - PIB) at Józefów.

Halogen free cables are applied in locations where, in case of fire, higher safety for human beings and expensive electronic equipment is required.

Functions of the cables are maintained – data are transmitted and power is supplied to equipment which must operate in fire conditions and during fire fighting (e.g. emergency lighting). The cables are flame retardant and their smoke emission is low, emitted fumes are non toxic and non corrosive.

The cables are resistant to water in accordance with PN-EN 50200 Annex E and can be used in fire protected rooms with fixed pressure water spraying fire extinguishing systems (sprinkler zones).

Cable circuits are protected by an overall electrostatic shield (ekw) against external electric field interferences.

The cables are suitable for fixed indoor installations.

CONSTRUCTION                                                                                                           

- bare annealed copper single wire round conductors,

- mica tape and halogen free compound insulation - colours in accordance with PN-92/T-90321 standard,

- insulated conductors twisted into pairs,

- pairs laid-up into a cable core,

- cable core wrapped in a polyester tape,

- overall electrostatic shield incorporating a plastic laminated metal foil and a tinned copper drain wire – only in HTKSHekw FE180 PH90/E30-E90,

- red cable sheath made of halogen free compound type HM2 according to EN 50290-2-27 and VDE 0250‑214 standard.

CHARACTERISTICS

Cable type

 

HTKSH FE180 PH90/E30-E90

HTKSHekw FE180 PH90/E30-E90

Conductor diameter

mm

0.8

1.0

1.4

1.8

2.3

2.8

0.8

1.0

1.4

1.8

2.3

2.8

Conductor cross-section

mm2

0.5

0.75

1.5

2.5

4

6

0.5

0.75

1.5

2.5

4

6

DC loop resistance at 20°C, maximum

Ω/km

75

48

24.5

14.9

9.3

6.3

75

48

24.5

14.9

9.3

6.3

Mutual capacitance

at 1 kHz

maximum

nF/km

120

120

120

120

120

120

200

200

200

200

200

200

average

60

70

70

70

100

100

90

130

130

130

150

150


Operating voltage    240 V

Voltage test    1.5 kV rms

Insulation resistance, minimum    500 MΩ·km

Inductance, approximate    0.7 mH/km

Corrosivity  of emitted gases per    PN-EN 60754-1, PN-EN 60754-2, IEC 60754-2

pH, approximate    6.8

conductivity, approximate    0.4 µS/mm

Smoke density per    PN-EN 61034-2, IEC 61034-2

light transmittance, minimum    70%

Operating temperature range

      during operation                  from - 30 to + 80°C
      during installation                 from   - 5 to + 50°C

Minimum bending radius              10 x cable diameter

Cable combustibility                    flame retardant

Combustibility tests                    PN-EN 60332-1-2, IEC 60332-1-2, PN-EN 60332-3-24, IEC 60332-3-24 (cat. C)

Circuit integrity *                           

             E30-E90                      DIN 4102-12

             PH90                          PN-EN 50200 or PN-EN 50362

Insulation integrity  FE180          IEC 60331-21; IEC 60331-11

Reference standards                  AT-0603-0098/2011/2016, WT-TK-43, PN-92/T-90321

*Circuit integrity is dependent on installation method.

The cable meets requirements of the low voltage directive 2014/35/EU

 

Cable type

Fire Load (appr.) kWh/m

HTKSH FE180 PH90/E30-E90 1 x 2 x 0.8

0.09

HTKSH FE180 PH90/E30-E90 2 x 2 x 0.8

0.17

HTKSH FE180 PH90/E30-E90 3 x 2 x 0.8

0.19

HTKSH FE180 PH90/E30-E90 4 x 2 x 0.8

0.23

HTKSH FE180 PH90/E30-E90 5 x 2 x 0.8

0.26

HTKSH FE180 PH90/E30-E90 7 x 2 x 0.8

0.34

HTKSH FE180 PH90/E30-E90 10 x 2 x 0.8

0.45

HTKSH FE180 PH90/E30-E90 1 x 2 x 1.0

0.10

HTKSH FE180 PH90/E30-E90 2 x 2 x 1.0

0.18

HTKSH FE180 PH90/E30-E90 3 x 2 x 1.0

0.21

HTKSH FE180 PH90/E30-E90 4 x 2 x 1.0

0.25

HTKSH FE180 PH90/E30-E90 5 x 2 x 1.0

0.32

HTKSH FE180 PH90/E30-E90 1 x 2 x 1.4

0.12

HTKSH FE180 PH90/E30-E90 2 x 2 x 1.4

0.22

HTKSH FE180 PH90/E30-E90 3 x 2 x 1.4

0.26

HTKSH FE180 PH90/E30-E90 4 x 2 x 1.4

0.33

HTKSH FE180 PH90/E30-E90 1 x 2 x 1.8

0.19

HTKSH FE180 PH90/E30-E90 2 x 2 x 1.8

0.36

HTKSH FE180 PH90/E30-E90 1 x 2 x 2.3

0.22

HTKSH FE180 PH90/E30-E90 1 x 2 x 2.8

0.25

HTKSHekw FE180 PH90/E30-E90 1 x 2 x 0.8

0.09

HTKSHekw FE180 PH90/E30-E90 2 x 2 x 0.8

0.17

HTKSHekw FE180 PH90/E30-E90 3 x 2 x 0.8

0.20

HTKSHekw FE180 PH90/E30-E90 4 x 2 x 0.8

0.23

HTKSHekw FE180 PH90/E30-E90 1 x 2 x 1.0

0.10

HTKSHekw FE180 PH90/E30-E90 2 x 2 x 1.0

0.19

HTKSHekw FE180 PH90/E30-E90 3 x 2 x 1.0

0.22

HTKSHekw FE180 PH90/E30-E90 4 x 2 x 1.0

0.25

HTKSHekw FE180 PH90/E30-E90 5 x 2 x 1.0

0.32

HTKSHekw FE180 PH90/E30-E90 8 x 2 x 1.0

0.42

HTKSHekw FE180 PH90/E30-E90 1 x 2 x 1.4

0.12

HTKSHekw FE180 PH90/E30-E90 2 x 2 x 1.4

0.22

HTKSHekw FE180 PH90/E30-E90 4 x 2 x 1.4

0.33

HTKSHekw FE180 PH90/E30-E90 5 x 2 x 1.4

0.38

HTKSHekw FE180 PH90/E30-E90 6 x 2 x 1.4

0.43

HTKSHekw FE180 PH90/E30-E90 1 x 2 x 1.8

0.19

HTKSHekw FE180 PH90/E30-E90 2 x 2 x 1.8

0.36

HTKSHekw FE180 PH90/E30-E90 1 x 2 x 2.3

0.22

HTKSHekw FE180 PH90/E30-E90 2 x 2 x 2.3

0.42

HTKSHekw FE180 PH90/E30-E90 1 x 2 x 2.8

0.25

Other diameters and pair counts available on request.

TECHNOKABEL S.A. reserves the right to change specifications without prior notice.