CONTROL AND POWER SUPPLY FLEXIBLE CABLES Technical Data sheet
 

 acrobat reader_50x50  

APPLICATIONS

YSLYCY-JZ 300/500 V, YSLYCY-OZ 300/500 V, YSLYCY-JB 300/500 V and YSLYCY‑OB 300/500 V are flexible, overall shielded cables designed for wet or dry locations and intended for control, protection and monitoring systems or power supply, all in power engineering. The cables are also intended for wiring industrial plants, such as production lines, air-conditioning equipment etc.

The overall shield protects the cables against external electromagnetic interferences and prevents emission of interferences produced in the cables.

Cable inner sheath offers enhanced protection against mechanical damage.

The cables are designed to offer high flexibility combined with tensile strength.

The cables are suitable for indoor and outdoor installations connecting fixed and movable equipment.  UV radiation protection is required for outdoor installations.

Cable outer sheath is oil-resistant.

CONSTRUCTION

- flexible, multiwire conductors, stranded of bare annealed copper wires (tin-plated on request), meeting requirements of class 5 per PN-EN 60228,

- PVC insulation - identification colour code:

    YSLYCY-OZ 300/500 V - black and white conductor number printed on it,

    YSLYCY‑OB 300/500 V - colours in accordance with PN-HD 308 standard, green-yellow protective conductor located in the outer layer in YSLYCY-JZ 300/500 V and  YSLYCY-JB 300/500 V  cable,

- insulated conductors laid-up in layers,

- inner PVC sheath,

- tinned copper wire braid shield of effective density coverage,

- PVC cable sheath, grey RAL 7001, other colours also available.

AVAILABLE UPON REQUEST

YSLYCY-JZ OR 300/500 V, YSLYCY-OZ OR 300/500 V, YSLYCY-JB OR 300/500 V and YSLYCY‑OB OR 300/500 V - cables designed for frequent contact with petroleum products, as in petrol stations and stores, where engine fuels and lubricants are pumped or handled. The cable sheath is then made of special PVC compound meeting oil resistance requirements of Polish standard PN-EN 60811-404.

YSLYSY-JZ 300/500 V, YSLYSY-OZ 300/500 V, YSLYSY-JB 300/500 V and YSLYSY‑OB 300/500 V  – cables of enhanced protection against mechanical damage, shielded with zinc-plated steel wire braid.

 

CHARACTERISTICS

Conductor cross-section

mm2

0.5

0.75

1.0

1.5

2.5

4.0

DC conductor resistance at 20°C, maximum

Ω/km

39.0

26.0

19.5

13.3

7.98

4.95

Conductor cross-section

mm2

6.0

10

16

25

35

50

DC conductor resistance at 20°C, maximum

Ω/km

3.30

1.91

1.21

0.780

0.554

0.386

 

Operating voltage Uo/U

Voltage test

Insulation resistance, minimum

Conductor temperature limit

        in work conditions

        at short-circuit

300/500 V

3.0 kV rms

20 MΩ·km

 

+ 70°C

+ 150°C

Operating temperature range

      for fixed installation

      for movable installation

Minimum bending radius

Cable combustibility

Combustibility tests

Reference standards

 

from - 40 to + 80°C

from   - 5 to + 70°C

10 x cable diameter

flame retardant

PN-EN 60332-1-2, IEC 60332-1-2

WT-TK-50

The cable meets requirements of the low voltage directive 2014/35/EU

Other cross-sections and conductor counts available on request.

TECHNOKABEL S.A. reserves the right to change specifications without prior notice.