CONTROL CABLES FOR INDUSTRIAL ELECTRONIC APPLICATIONS Technical Data sheet
 

 

 acrobat reader_50x50  

APPLICATIONS

TECHNOTRONIK LiYY-Nr are control cables intended for control and instrumentation circuits, for signal, monitoring and data processing systems and for analogue or digital data transmission, all for industrial electronic applications.

The cables are designed to offer high flexibility and small outer diameter combined with tensile strength.

The cables can also be used for power supply to small auxiliary devices on condition that current-carrying capacity limit (see our Technical Guide) is not exceeded.

The cables are suitable for indoor installations connecting fixed and movable equipment.

Cable outer sheath is oil-resistant.

CONSTRUCTION

-   flexible, multiwire conductors, stranded of bare annealed copper wires (tin-plated on request), meeting requirements of class 5 per PN-EN 60228,

-   black PVC insulation and white conductor numbers printed on it for identification,

-   insulated conductors laid-up in layers,

-   PVC cable sheath, grey RAL 7001, other colours also available.

AVAILABLE UPON REQUEST

TECHNOTRONIK LiYY-Nr-O - cables designed for frequent contact with petroleum products, as in petrol stations and stores, where engine fuels and lubricants are pumped or handled. The cable sheath is then made of special PVC compound meeting oil resistance requirements of Polish standard PN-EN 60811-404.

TECHNOTRONIK LiY11Y-Nr - polyurethane sheathed cables of enhanced protection against mechanical damage, particularly to abrasion and tear, also resistant to oils, petrol, bacteria and ultraviolet radiation.

TECHNOTRONIK LiHH-Nr - halogen free cables, applied when higher safety in case of fire is required. The cables are flame retardant, their smoke emission in fire is low and released gases are not corrosive.

TECHNOTRONIK IB-LiYY-Nr - specially designed intrinsically safe cable.

CHARACTERISTICS

Conductor cross-section

mm2

0.5

0.75

1.0

1.5

2.5

Operating voltage, peak value

V

500

500

500

500

500

Voltage test

V rms

1500

1500

1500

1500

1500

DC conductor resistance at 20°C, maximum

Ω/km

39.0

26.0

19.5

13.3

7.98

Capacitance between conductors at 1 kHz, appr.

nF/km

110

130

130

140

140

 

Operating voltage Uo/U

Insulation resistance, minimum

Inductance, approximate

Impedance, approximate

300/300 V

20 MΩ·km

0.7 mH/km

80 Ω

Operating temperature range

      for fixed installation

      for movable installation

Minimum bending radius

Cable combustibility

Combustibility tests

Reference standards

 

from - 30 to + 80°C

from   - 5 to + 70°C

7.5 x cable diameter

flame retardant

PN-EN 60332-1-2, IEC 60332-1-2

DIN VDE 0812, DIN VDE 0814

The cable meets requirements of the low voltage directive 2014/35/EU

Other cross-sections and conductor counts available on request.

TECHNOKABEL S.A. reserves the right to change specifications without prior notice.