CONTROL AND POWER SUPPLY FLEXIBLE CABLES | Technical Data sheet |
|
|
APPLICATIONS
HSLH-JZ 300/500 V, HSLH-OZ 300/500 V, HSLH-JB 300/500 V and HSLH‑OB 300/500 V are flexible cables designed for wet or dry locations and intended for control, protection and monitoring systems or power supply, all in power engineering. The cables are also intended for wiring industrial plants, such as production lines, air-conditioning equipment etc.
Halogen free cables, applied when higher safety in case of fire is required. The cables are flame retardant, their smoke emission in fire is low and released gases are not corrosive.
The cables are designed to offer high flexibility combined with tensile strength.
The cables are suitable for indoor installations connecting fixed and movable equipment.
Cable outer sheath is oil-resistant.
CONSTRUCTION
- flexible, multiwire conductors, stranded of bare annealed copper wires (tin-plated on request), meeting requirements of class 5 per PN-EN 60228,
- insulation made of halogen free compound (HFFR), identification colour code:
HSLH-OZ 300/500 V - black and white conductor number printed on it,
HSLH‑OB 300/500 V - colours in accordance with PN-HD 308 standard, green-yellow protective conductor located in the outer layer in HSLH-JZ 300/500 V and HSLH-JB 300/500 V cable,
- insulated conductors laid-up in layers,
- cable sheath made of halogen free compound (HFFR), grey (RAL 7001), other colours also available.
CHARACTERISTICS
Conductor cross-section |
mm2 |
0.5 |
0.75 |
1.0 |
1.5 |
2.5 |
4.0 |
DC conductor resistance at 20°C, maximum |
Ω/km |
39.0 |
26.0 |
19.5 |
13.3 |
7.98 |
4.95 |
Conductor cross-section |
mm2 |
6.0 |
10 |
16 |
25 |
35 |
50 |
DC conductor resistance at 20°C, maximum |
Ω/km |
3.30 |
1.91 |
1.21 |
0.780 |
0.554 |
0.386 |
Operating voltage Uo/U |
300/500 V |
Voltage test |
3,0 kV sk |
Insulation resistance, minimum |
20 MΩ·km |
Conductor temperature limit |
|
in work conditions |
+ 70°C |
at short-circuit |
+ 150°C |
Operating temperature range |
|
for fixed installation |
from - 40 to + 80°C |
for movable installation |
from - 5 to + 70°C |
Minimum bending radius |
7,5 x cable diameter |
Corrosivity of emitted gases per |
PN-EN 60754-1, PN-EN 60754-2, IEC 60754-2 |
pH, appr. |
6,8 |
conductivity appr. |
0,4 µS/mm |
Smoke density |
PN-EN 61034-2, IEC 61034-2 |
light transmittance, min |
70% |
Cable combustibility |
flame retardant |
Combustibility tests |
PN-EN 60332-1-2, IEC 60332-1-2 |
Reference standards |
WT-TK-50 |
The cable meets requirements of the low voltage directive 2014/35/EU
Other cross-sections and conductor counts available on request.
TECHNOKABEL S.A. reserves the right to change specifications without prior notice.