CONTROL AND POWER SUPPLY FLEXIBLE CABLES | Technical Data sheet |
|
|
APPLICATIONS
HSLCH-JZ 0,6/1 kV, HSLCH-OZ 0,6/1 kV, HSLCH-JB 0,6/1 kV and HSLCH‑OB 0,6/1 kV are flexible, overall shielded cables intended for control, protection and monitoring systems or power supply, all in power engineering. The cables are also intended for wiring industrial plants, such as production lines, air-conditioning equipment etc.
The overall shield protects the cables against external electromagnetic interferences and prevents emission of interferences produced in the cables.
Halogen free cables, applied when higher safety in case of fire is required. The cables are flame retardant, their smoke emission in fire is low and released gases are not corrosive.
The cables are designed to offer high flexibility combined with tensile strength.
The cables are suitable for indoor and outdoor installations in dry and wet locations, also for direct earth burial.
Sheathing black halogen free material is resistant to UV radiation.
Cable outer sheath is oil-resistant.
CONSTRUCTION
- flexible, multiwire conductors, stranded of bare annealed copper wires (tin-plated on request), meeting requirements of class 5 per PN-EN 60228,
- insulation made of halogen free compound (HFFR), identification colour code:
HSLCH-OZ 0,6/1 kV - black and white conductor number printed on it,
HSLCH‑OB 0,6/1 kV - colours in accordance with PN-HD 308 standard, green-yellow protective conductor located in the outer layer in HSLCH-JZ 0,6/1 kV and HSLCH‑JB 0,6/1 kV cable,
- insulated conductors laid-up in layers,
- cable core wrapped in polyester tape,
- tinned copper wire braid shield of effective density coverage,
- black cable sheath made of halogen free compound (HFFR).
CHARACTERISTICS
Conductor cross-section |
mm2 |
0.5 |
0.75 |
1.0 |
1.5 |
2.5 |
4.0 |
DC conductor resistance at 20°C, maximum |
Ω/km |
39.0 |
26.0 |
19.5 |
13.3 |
7.98 |
4.95 |
Conductor cross-section |
mm2 |
6.0 |
10 |
16 |
25 |
35 |
50 |
DC conductor resistance at 20°C, maximum |
Ω/km |
3.30 |
1.91 |
1.21 |
0.780 |
0.554 |
0.386 |
Operating voltage Uo/U |
0.6/1 kV |
Voltage test |
4 kV rms |
Insulation resistance, minimum |
20 MΩ·km |
Conductor temperature limit |
|
in work conditions |
+ 70°C |
at short-circuit |
+ 160°C |
Operating temperature range |
|
for fixed installation |
from - 40 to + 80°C |
for movable installation |
from - 5 to + 70°C |
Minimum bending radius |
10 x cable diameter |
Corrosivity of emitted gases per |
PN-EN 60754-1, PN-EN 60754-2, IEC 60754-2 |
pH, appr. |
6,8 |
conductivity appr. |
0,4 µS/mm |
Smoke density |
PN-EN 61034-2, IEC 61034-2 |
light transmittance, min |
70% |
Cable combustibility |
flame retardant |
Combustibility tests |
PN-EN 60332-1-2, IEC 60332-1-2 |
Reference standards |
WT-TK-50 |
The cable meets requirements of the low voltage directive 2014/35/EU
Other cross-sections and conductor counts available on request.
TECHNOKABEL S.A. reserves the right to change specifications without prior notice.