HALOGEN FREE CONTROL CABLES FOR INDUSTRIAL ELECTRONIC APPLICATIONS Technical Data sheet
 

 

 acrobat reader_50x50  

APPLICATIONS

TECHNOTRONIK LiHCH are halogen free, overall shielded control cables intended for control and instrumentation circuits, for signal, monitoring and data processing systems and for analogue or digital data transmission, all for industrial electronic applications.

Halogen free cables, applied when higher safety in case of fire is required. The cables are flame retardant, their smoke emission in fire is low and released gases are not corrosive.

To achieve high analogue or digital data transmission performance the cable is protected against external electromagnetic interferences by an overall shield.

The cables are designed to offer high flexibility and small outer diameter combined with tensile strength.

The cables are suitable for connecting fixed and movable equipment inside rail vehicles, subway trains, in trams, as well as for indoor installations.

CONSTRUCTION                                                                                                           

- flexible, multiwire conductors, stranded of bare annealed copper wires (tin-plated on request), meeting requirements of class 5 per PN-EN 60228,

- insulation made of halogen free compound (HFFR) - identification colour code in accordance with DIN VDE 47100,

- insulated conductors laid-up in layers,

- cable core wrapped in polyester tape,

- tinned copper wire braid shield of effective density coverage,

- cable sheath made of halogen free compound (HFFR), grey (RAL 7001), other colours also available.

AVAILABLE UPON REQUEST

TECHNOTRONIK LiHCEH - cables with flexible drain wire stranded of tin-plated annealed copper wires, laid under a shield.

TECHNOTRONIK IB-LiHCH - specially designed intrinsically safe cable.

CHARACTERISTICS

Conductor cross-section

mm2

0.5

0.75

1.0

1.5

2.5

DC conductor resistance at 20°C, maximum

Ω/km

39.0

26.0

19.5

13.3

7.98

Capacitance between conductors at 1 kHz, appr.

nF/km

100

110

140

130

150

 

Operating voltage Uo/U

300/300 V

Insulation resistance, minimum

20 MΩ·km

Voltage test

1.5 kV rms

Inductance, approximate

0.7 mH/km

Impedance, approximate

80 Ω

Corrosivity of emitted gases per

PN-EN 60754-1, PN-EN 60754-2, IEC 60754-2

Operating temperature range

for fixed installation

from - 30 to + 70°C

for movable installation

from  - 5 to + 70°C

Minimum bending radius

10 x cable diameter

pH, appr.

6,8

conductivity appr.

0,4 µS/mm

Smoke density

PN-EN 61034-2, IEC 61034-2

light transmittance, min

70%

Cable combustibility

flame retardant

Combustibility tests

PN-EN 60332-1-2, IEC 60332-1-2

Reference standards

DIN VDE 0812, DIN VDE 0814

The cable meets requirements of the low voltage directive 2014/35/EU

Other cross-sections and conductor counts available on request.

TECHNOKABEL S.A. reserves the right to change specifications without prior notice.