CONTROL AND POWER SUPPLY FLEXIBLE CABLES Technical Data sheet
 

 acrobat reader_50x50  

APPLICATIONS

TECHNOFLEKS LiYCY-P 300/500 V and TECHNOFLEKS LiYCY-P-Nr 300/500 V are multipair flexible, overall shielded cables designed for control, protection and monitoring systems or power supply, all in power engineering.

Paired structure decreases mutual influence between signals transmitted along the cable.

The overall shield protects the cables against external electromagnetic interferences and prevents emission of interferences produced in the cables.

The cables are suitable for indoor installations connecting fixed and movable equipment.

Cable outer sheath is oil-resistant.

 

CONSTRUCTION

- flexible, multiwire conductors, stranded of bare annealed copper wires (tin-plated on request), meeting requirements of class 5 per PN-EN 60228,

- PVC insulation - identification colour code in accordance with DIN VDE 47100in TECHNOFLEKS LiYCY-P 300/500 V, black and brown PVC insulation and white pair numbers printed on it for identification in TECHNOFLEKS LiYCY-P-Nr 300/500 V,

- insulated conductors twisted into pairs,

- pairs laid-up in layers,

- cable core wrapped in polyester tape,

- tinned copper wire braid shield of effective density coverage,

- PVC cable sheath, grey RAL 7001, other colours also available.

AVAILABLE UPON REQUEST

TECHNOFLEKS LiYCEY-P 300/500 V and TECHNOFLEKS LiYCEY-P-Nr 300/500 V - cables with flexible drain wire stranded of tin-plated annealed copper wires, laid under a shield.

TECHNOFLEKS LiYCY-P-O 300/500 V and TECHNOFLEKS LiYCY-P-Nr-O 300/500 V - cables designed for frequent contact with petroleum products, as in petrol stations and stores, where engine fuels and lubricants are pumped or handled. The cable sheath is then made of special PVC compound meeting oil resistance requirements of Polish standard PN-EN 60811-404.

TECHNOFLEKS LiYC11Y-P 300/500 V and TECHNOFLEKS LiYC11Y-P-Nr 300/500 V – polyurethane sheathed cables of enhanced protection against mechanical damage, particularly to abrasion and tear, also resistant to oils, petrol, bacteria and ultraviolet radiation.

TECHNOFLEKS LiYCYv-P 300/500 V and TECHNOFLEKS LiYCYv-P-Nr 300/500 V - cables with enhanced PVC sheath, suitable for outdoor installation and direct earth burial.

CHARACTERISTICS

Conductor cross-section

mm2

0.5

0.75

1.0

1.5

2.5

DC loop resistance at 20°C, maximum

Ω/km

78.0

52.0

39.0

26.6

16.0

 

Operating voltage Uo/U

Voltage test

Insulation resistance, minimum

Conductor temperature limit

        in work conditions

        at short-circuit

300/500 V

3.0 kV rms

20 MΩ·km

 

+ 70°C

+ 150°C

Operating temperature range

      for fixed installation

      for movable installation

Minimum bending radius

Cable combustibility

Combustibility tests

Reference standards

 

from - 30 to + 80°C

from   - 5 to + 70°C

10 x cable diameter

flame retardant

PN-EN 60332-1-2, IEC 60332-1-2

DIN VDE 0245, DIN VDE 0250, DIN VDE 0281

The cable meets requirements of the low voltage directive 2014/35/EU

Other cross-sections and pair counts available on request.

TECHNOKABEL S.A. reserves the right to change specifications without prior notice.